Standard Features
  • 316L Stainless Steel on all Wetted Surfaces
  • Built in accordance with A.S.M.E. Miniature Boiler Code
  • UL Listed and labeled under UL 834
  • Dual Pressure Controls (UL 353)
  • High Pressure Safety Reset. (UL 353)
  • Low Level Cut-Off (LLCO)
  • 15 psi Safety Relief Valve (A.S.M.E. Section I - V-Stamp)

Recommended Options (Non-Standard)
  • Spare Parts Package
  • Single Service Transformer
Unit of Measure

Specifications

Brands

N/A Electro-Steam™

Electrical Power Rating

N/A 180 kW
Power Supply Voltage1 N/A 208 VAC230 VAC380 VAC415 VAC440 VAC480 VAC600 VAC
Phase2 N/A 3

Frequency

N/A 50 Hz60 Hz

Boiler Horse Power

N/A 18 bhp
Steam Capacity3 N/A 621 lb/hr281.68 kg/h

Water Consumption

N/A 74.41 gal/h281.68 L/h

Note for Water Consumption

N/A Calculations are based off of a 212°F boiler feed-water temperature. Boiler feed-water temperatures that range between 60°F and 140°F, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140°F.

Gross British Thermal Units (BTU) Output

N/A 602556 Btu/hr

Maximum Boiler Pressure

N/A 100 psi

Operating Pressure

N/A 0 to 80 psi

Maximum Boiler Capacity

N/A 26.50 gal

Boiler Fill Capacity

N/A 22.00 gal
Boiler Material4 N/A 316L Stainless Steel

Cabinet Material

N/A 304 Stainless Steel

Plumbing Material

N/A 316L Stainless Steel (Schedule 40)

Industry Standards

N/A American Society of Mechanical Engineers (ASME) - Boiler and Pressure Vessel Code American Society of Mechanical Engineers (ASME) - CSD-1 Underwriters Laboratories (UL) Canadian Underwriters Laboratories (cUL)

Amperage

Amperage at 208 VAC (3Ø Phase)

N/A 499.6 A (249.8 A per Box)

Amperage at 240 VAC (3Ø Phase)

N/A 471.5 A (235.7 A per Box)

Amperage at 380 VAC (3Ø Phase)

N/A 273.5 A (136.7 A per Box)

Amperage at 415 VAC (3Ø Phase)

N/A 250.4 A (125.2 A per Box)

Amperage at 440 VAC (3Ø Phase)

N/A 236.2 A (118.1 A per Box)

Amperage at 480 VAC (3Ø Phase)

N/A 216.5 A (108.3 A per Box)

Amperage at 600 VAC (3Ø Phase)

N/A 173.2 A (86.6 A per Box)

Dimensions

Length

N/A 51 in

Width

N/A 30 in

Height

N/A 37 in

Minimum Clearance

Total Length

N/A 120 in

Total Width

N/A 60 in

Total Height

N/A 45 in

Plumbing Connection Sizes

Water Inlet

N/A 1/2" National Pipe Thread (NPT) (Female) - Street Elbow, 316L Stainless Steel (SS)

Steam Outlet

N/A 3/4" National Pipe Thread (NPT) (Female) - Ball Valve, 316L SS

Safety Valve

N/A 1-1/4" National Pipe Thread (NPT) (Female) - Safety Valve, 316L Stainless Steel (SS) Trim (Wetted Surfaces), Brass Body.

Drain

N/A 1" National Pipe Thread (NPT) (Female) - Ball Valve, 316L Stainless Steel (SS)

Options

Spare Parts Package Includes

N/A
  • 18-Month Warranty (12-Month Standard)
  • (2) Electric Heaters and (2) Heater Gaskets
  • (2) Sight Glass Tubes and (4) Washers
  • (1) Pressure Control
  • (1) Contactor

Single Service Transformer

N/A Supplied standard with all portable steam generators, the Transformer steps down the primary high voltage supplied for the heaters, in order to provide 120VAC 1Ø for the controls; with this option, only the two (2) primary high voltage supplies are required.
Manual Low Water Reset5 N/A Manual Low Water Reset trips if the electric heaters shut-off because of a low water condition. Reset must be manually pressed to resume steam production.

Portable Mounting Includes

N/A
  • Wheels
  • Push Handle
  • Single Service Transformer Option

Water Feed Booster Pump

N/A Supplied standard on any steam generator with an operating pressure higher than 15 psi. The Water Feed Booster Pump increases your incoming water pressure to overcome the operating pressure of the steam generator. The Pump requires a 5-150 psi water supply with a minimum flow rate of 2 gpm.
  • 1 Electro-Steam™ 100-240 kW electric steam generators require three (3) power supplies: Two (2) primary high voltage supplies and one (1) secondary 120 VAC 1Ø, 50/60 Hz supply. Each generator is custom built to accommodate two (2) supplies of only one (1) customer specific high voltage for the heaters. 120 VAC 1Ø, 50/60 Hz must also be supplied for the controls, unless the Single Service Transformer option is added.
  • 2 Three Phase (3Ø) primary high voltage is standard, but steam generators with a power rating of 30 kW or lower are also available in Single Phase (1Ø) upon request.
  • 3 Calculations are based off of a 212 ºF boiler feed-water temperature. Boiler feed-water temperatures that range between 60 ºF and 140 ºF, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140 ºF.
  • 4 Wetted Surfaces.
  • 5 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this Reset Button is required as per your local boiler codes, simply remove the jumper wire from the back of the Reset Button.