VB 10-40 Electric Steam Generators
VB-15 15 Kilowatt (kW) Rating High Pressure Electric Steam Generator
Standard Features
| ASME Certified | High Pressure Safety Reset |
| UL Listed and labeled under UL 834 | Dual Pressure Controls (UL 353) |
| Low Level Cut-Off (LLCO) (UL 353) | Safety Relief Valve possessing the ASME V Mark |
Recommended Options (Non-Standard)
| Spare Parts Package | Motorized Automatic Flush and Drain (MAFD) |
Specifications
| Brand | Electro-Steam™ |
|---|---|
| Electrical Power | 15 kW |
| Power Supply Voltage1 | 208 VAC, 230 VAC, 380 VAC, 415 VAC, 440 VAC, 480 VAC, 600 VAC |
| Phase | 3 |
| Frequency | 50 Hz, 60 Hz |
| Boiler Horse Power | 1.5 bhp |
| Steam Capacity2 | 51.75 lb/hr (23.47 kg/hr) |
| Water Consumption | 6.2 gal/hr (23.47 L/hr) |
| Gross British Thermal Units (BTU) Output | 50,213 Btu/hr |
| Maximum Boiler Pressure | 100 psi |
| Operating Pressure | 0 to 80 psi |
| Note for Operating Pressure | Factory Set at 80 psi |
| Maximum Boiler Capacity | 6 gal |
| Boiler Fill Capacity | 4.2 gal |
| Boiler Material3 | Carbon Steel |
| Cabinet Material | 304 Stainless Steel |
| Plumbing Material | Brass, Carbon Steel (Schedule 40) |
Amperage by Voltage (3Ø Phase)
| 208 VAC | 240 VAC | 380 VAC | 415 VAC | 440 VAC | 480 VAC | 600 VAC |
|---|---|---|---|---|---|---|
| 41.60 A | 39.30 A | 22.80 A | 20.90 A | 19.70 A | 18.00 A | 14.40 A |
Plumbing Connection Sizes
| Water Inlet | 3/8" NPT (National Pipe Thread) (Female) - Y-Strainer, Brass |
|---|---|
| Steam Outlet | 1/2" NPT (National Pipe Thread) (Female) - Ball Valve, Brass |
| Safety Valve | 3/4" NPT (National Pipe Thread) (Female) - Safety Valve, Brass |
| Drain | 3/4" National Pipe Thread (NPT) (Female) - Ball Valve, Brass |
| Additional Drain (Motorized Automatic Flush and Drain (MAFD) Option Included) | 3/4" NPT (National Pipe Thread) (Female) - Motorized Valve, Brass |
Options
| Spare Parts Package Includes | 18-Month Warranty (12-Month Standard) (2) Electric Heaters and (2) Heater Gaskets (2) Sight Glass Tubes and (4) Washers (1) Pressure Control (1) Contactor |
|---|---|
| Manual Low Water Reset4 | Manual Low Water Reset trips if the electric heaters shut-off because of a low water condition. Reset must be manually pressed to resume steam production. |
- 1 Each Electro-Steam™ electric steam generator requires two (2) power supplies: One (1) customer specific primary high voltage supply for the heaters and one (1) secondary 120 VAC 1Ø, 50/60 Hz supply for the Controls.
- 2 Calculations are based off of a 212ºF boiler feed-water temperature. Boiler feed-water temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140ºF.
- 3 Wetted Surfaces
- 4 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this Reset Button is required as per your local boiler codes, simply plug the two attached wires into the PC-Board terminals labeled "Reset".