LB 40-60 Electric Steam Generators

LB-60 (H) 60 Kilowatt (kW) Electrical Power Rating Electric Steam Generator

LB-60 (H), 60 Kilowatt (kW) Electrical Power Rating Electric Steam Generator

Dimensions

Length
(No Options)
52 in
Length
(with MAFD option)
55 in
Width
(No Options)
26 in
Width
(with MAFD option)
29 in
Height36 in

Minimum Clearance

Total Height45 in
Total Length96 in
Total Width58 in

Industry Standards

  • American Society of Mechanical Engineers (ASME) - Boiler and Pressure Vessel Code
  • American Society of Mechanical Engineers (ASME) - CSD-1
  • Canadian Underwriters Laboratories (cUL)
  • Underwriters Laboratories (UL)
ASME UL Listed

Standard Features

ASME Certified High Pressure Safety Reset
UL Listed and labeled under UL 834 Dual Pressure Controls (UL 353)
Low Level Cut-Off (LLCO) (UL 353) Safety Relief Valve possessing the ASME V Mark

Recommended Options (Non-Standard)

Spare Parts Package Motorized Automatic Flush and Drain (MAFD)
Single Service Transformer 5-Micron Water Filter

Specifications

BrandElectro-Steam™
VariantHigh Pressure
Electrical Power60 kW
Power Supply Voltage1208 VAC, 230 VAC, 380 VAC, 415 VAC, 440 VAC, 480 VAC, 600 VAC
Phase3
Frequency50 Hz, 60 Hz
Boiler Horse Power6.0 bhp
Steam Capacity2207.0 lb/hr (93.89 kg/hr)
Water Consumption24.8 gal/hr (93.88 L/hr)
Gross British Thermal Units (BTU) Output200,852 Btu/hr
Maximum Boiler Pressure100 psi
Operating Pressure0 to 80 psi
Note for Operating PressureFactory Set at 80 psi
Maximum Boiler Capacity15 gal
Boiler Fill Capacity11 gal
Boiler Material3Carbon Steel
Cabinet Material304 Stainless Steel
Plumbing MaterialBrass (Schedule 40), Carbon Steel (Schedule 40)

Amperage by Voltage (3Ø Phase)

208 VAC240 VAC380 VAC415 VAC440 VAC480 VAC600 VAC
166.50 A 157.20 A 91.20 A 83.50 A 78.70 A 72.20 A 57.70 A

Plumbing Connection Sizes

Water Inlet 1/2" NPT (National Pipe Thread) (Female) - Y-Strainer, Brass
Steam Outlet 3/4" NPT (National Pipe Thread) (Female) - Ball Valve, Brass
Safety Valve 3/4" NPT (National Pipe Thread) (Female) - Safety Valve, Brass
Drain 1" National Pipe Thread (NPT) (Female) - Ball Valve, Brass
Additional Drain (Motorized Automatic Flush and Drain (MAFD) Option Included) 1" NPT (National Pipe Thread) (Female) - Motorized Valve, Brass

Options

Spare Parts Package Includes 18-Month Warranty (12-Month Standard)
(2) Electric Heaters and (2) Heater Gaskets
(2) Sight Glass Tubes and (4) Washers
(1) Pressure Control
(1) Contactor
Motorized Automatic Flush and Drain (MAFD) During Start-Up before steam pressure is accumulated, the Motorized Automatic Flush and Drain option cycles fresh water through the boiler for 0-300 seconds (Factory set for 180 seconds or three (3) minutes). As old water is drained out, fresh water will be cycled in. This drain valve will not open if boiler pressure exceeds 5 psi, and the electric heaters are locked out during flush cycle.
Single Service Transformer Supplied standard with all portable steam generators, the Single Service Transformer steps down the primary high voltage to provide 120 VAC Single Phase (1Ø) to the controls; with this option, only the one (1) primary high voltage supply is required.
5-Micron Water Filter 2-stage, 5-micron water filter installed into incoming water line to reduce sediment, dirt, rust, chlorine, and even odor from incoming water supply.
Manual Low Water Reset4 Manual Low Water Reset trips if the electric heaters shut-off because of a low water condition. Reset must be manually pressed to resume steam production.
Portable Mounting Includes Wheels
Push Handle
Single Service Transformer Option
Water Feed Booster Pump Supplied standard on any steam generator with an operating pressure higher than 15 psi. The Water Feed Booster Pump increases your incoming water pressure to overcome the operating pressure of the steam generator. The Pump requires a 5-150 psi water supply with a minimum flow rate of 2 gpm.
  • 1 Each Electro-Steam™ electric steam generator requires two (2) power supplies: One (1) primary high voltage supply and one (1) secondary 120 VAC 1Ø, 50/60 Hz supply. Each generator is custom built to accommodate only one (1) customer specific high voltage supply for the heaters. 120 VAC 1Ø, 50/60 Hz must also be supplied for the controls, unless the Single Service Transformer option is added.
  • 2 Calculations are based off of a 212ºF boiler feed-water temperature. Boiler feed-water temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140ºF.
  • 3 Wetted Surfaces
  • 4 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this Reset Button is required as per your local boiler codes, simply plug the two attached wires into the PC-Board terminals labeled "Reset".