Standard Features:
  • 316L Stainless Steel on all Wetted Surfaces
  • With the exception of our hawk series, all of our steam generators are built by an ASME Certificate holder in accordance with ASME BPVC Section I – Rules for Construction of Power Boilers (“ASME BPVC Section I”).  They also comply with the requirements outlined in The National Board Synopsis of Boiler and Pressure Vessel Laws, Rules and Regulations (NB-370) RULES FOR CONSTRUCTION AND STAMPING section, which for many jurisdictions include but are not limited to ASME BPVC Section I, ASME CSD-1, ASME B31.1, and REGISTRATION WITH THE NATIONAL BOARD.
  • High Pressure Safety Reset
  • UL Listed and labeled under UL 834
  • Dual Pressure Controls (UL 353)
  • Low Level Cut-Off (LLCO)
  • Safety Relief Valve possessing the ASME V Mark (these valves are built by a manufacturer holding a valid ASME Certificate of Authorization).

Recommended Options (Non-Standard)
  • Spare Parts Package
  • Single Service Transformer
Click here to read the NB-370 synopsis.

Unit of Measure

Specifications

Brands

N/A Electro-Steam™

Variant

N/A Low Pressure

Electrical Power Rating

N/A 60 kW
Power Supply Voltage1 N/A 208 VAC230 VAC380 VAC415 VAC440 VAC480 VAC600 VAC

Phase

N/A 3

Frequency

N/A 50 Hz60 Hz

Boiler Horse Power

N/A 6.0 bhp
Steam Capacity2 N/A 207.0 lb/hr93.89 kg/hr

Water Consumption

N/A 24.8 gal/hr93.89 L/hr

Note for Water Consumption

N/A Calculations are based off of a 212ºF boiler feed-water temperature. Boiler feed-water temperatures that range between 60ºF and 140ºF, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140ºF.

Gross British Thermal Units (BTU) Output

N/A 200,852 Btu/hr

Maximum Boiler Pressure

N/A 15 psi

Operating Pressure

N/A 0 to 11 psi

Maximum Boiler Capacity

N/A 15 gal

Boiler Fill Capacity

N/A 11 gal
Boiler Material 3 N/A 316L Stainless Steel

Cabinet Material

N/A 304 Stainless Steel

Plumbing Material

N/A 316L Stainless Steel (Schedule 40)

Industry Standards

N/A American Society of Mechanical Engineers (ASME) - Boiler and Pressure Vessel Code American Society of Mechanical Engineers (ASME) - CSD-1 Canadian Underwriters Laboratories (cUL) Underwriters Laboratories (UL)

Amperage

Amperage at 208 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 166.50 A

Amperage at 240 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 157.20 A

Amperage at 380 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 91.20 A

Amperage at 415 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 83.50 A

Amperage at 440 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 78.70 A

Amperage at 480 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 72.20 A

Amperage at 600 Volt (V) Alternating Current (AC) Voltage (3Ø Phase)

N/A 57.70 A

Dimensions

Length

N/A 52 in

Width

N/A 26 in

Height

N/A 36 in

Minimum Clearance

Total Length

N/A 96 in

Total Width

N/A 58 in

Total Height

N/A 45 in

Plumbing Connection Sizes

Water Inlet

N/A 1/2" National Pipe Thread (NPT) (Female) - Street Elbow, 316L Stainless Steel (SS)

Steam Outlet

N/A 3/4" National Pipe Thread (NPT) (Female) - Ball Valve, 316L SS

Safety Valve

N/A 3/4" National Pipe Thread (NPT) (Female) - Safety Valve, 316L Stainless Steel (SS) Trim (Wetted Surfaces), Brass Body.

Drain

N/A 1" National Pipe Thread (NPT) (Female) - Ball Valve, 316L Stainless Steel (SS)

Options

Spare Parts Package Includes

N/A
  • 18-Month Warranty (12-Month Standard)
  • (2) Electric Heaters and (2) Heater Gaskets
  • (2) Sight Glass Tubes and (4) Washers
  • (1) Pressure Control
  • (1) Contactor

Single Service Transformer

N/A Supplied standard with all portable steam generators, the Transformer steps down the primary high voltage supplied for the heaters, in order to provide 120 VAC1Ø for the controls; with the option, only the one (1) primary high voltage supply is required.
Manual Low Water Reset4 N/A Manual Low Water Reset trips if the electric heaters shut-off because of a low water condition. Reset must be manually pressed to resume steam production.

Portable Mounting Includes

N/A
  • Wheels
  • Push Handle
  • Single Service Transformer Option

Water Feed Booster Pump

N/A The minimum requirement for your water pressure is the operating pressure +25 psi; if your water pressure is below this requirement, this option must be added. The Water Feed Booster Pump increases your incoming water pressure to overcome the operating pressure of the steam generator. The Pump requires a 5-150 psi water supply with a minimum flow rate of 2 gpm.
  • 1 Each Electro-Steam™ electric steam generator requires two (2) power supplies: One (1) primary high voltage supply and one (1) secondary 120 VAC 1Ø, 50/60 Hz supply. Each generator is custom built to accommodate only one (1) customer specific high voltage supply for the heaters. 120 VAC 1Ø, 50/60 Hz must also be supplied for the controls, unless the Single Service Transformer option is added.
  • 2 Calculations are based off of a 212 ºF boiler feed-water temperature. Boiler feed-water temperatures that range between 60 ºF and 140 ºF, are approximately 80% to 90% of the calculated values shown. Boiler feed-water must not exceed 140 ºF.
  • 3 Wetted Surfaces.
  • 4 A Manual Low Water Reset Button is supplied standard with every steam generator, but it is disabled. If this Reset Button is required as per your local boiler codes, simply remove the jumper wire from the back of the Reset Button.